| Numéro de pièce du fabricant | 2744403 |
| Série | SUBCON-PLUS-PROFIB/PG |
| Type de Connecteur | D-SUB Bus Connector (Fieldbus Specific) |
| Nombre d'aiguilles | 9 Positions (DE Series) |
| Interface | Male Connector (Pin/Socket) |
| Protocole | PROFIBUS DP |
| Taux de transfert de données | 12 Mbps |
| Angle de Sortie du Câble | 35° (right angle/tilted out line) |
| Connecteur | Spring-cage connection |
| Surface Transversale Maximale du Conducteur | 0.12 - 0.5 mm² (26 - 20 AWG) |
| Spécifications | 5 mm |
| Interface matériel | 9-Pin D-SUB Female Connector (for Programming/Service Equipment) |
| Résistance | Integrated active termination resistor (390/220/390 Ω), switchable by dip switch |
| Nombre de broches | 3, 5, 6, 8 (compliant with PROFIBUS standard) |
| Matériau | Metal (zinc alloy die casting/metalized), providing 360° shielding |
| Tension | 60 V AC/DC (compliant with D-SUB standard rated values) |
| Courant Nominal | 1 A (Per Contact) |
| Température de Fonctionnement | -20°C ~ +70°C |
| Indice de Protection | IP20 (mounted condition) |
| Installation | cable installation / panel installation (optional accessories) |
| Norme de conformité | RoHS compliant, UL certified (E-file), CE |
| Unité de conditionnement | 1 Piece |
N° Fabricant
2744403SUBCON-PLUS-PROFIB/PG
Véhicules Compatibles
PROFIBUS DP fieldbus networkPLC communication module connectionindustrial automation control cabinet wiringRS-485 bus terminal equipment
Systèmes Électriques et Électroniques - Encyclopédie Industrielle
Phoenix Contact 2744403 SUBCON-PLUS-PROFIB/PG designed for PROFIBUS DP fieldbus, supporting 12 Mbps high-speed communication. Integrated with 9-pin D-SUB male connector, programming device interface (PG interface), and switchable terminal resistor with spring clamp wire technology, 35° angle wiring, metal shell shielding against interference, meeting the wiring requirements of harsh industrial automation field environments.